Most parts ship same day and arrive within 2 business days!
Honeywell R7847A1033 Rectification Flame Amplifier
Have a question? Our team is here to help! Chat with us or call us: 806-763-9323 / If you need Next Day Shipping, call us!
Sign up to be the first to know when it's back in stock.
Pickup currently unavailable at Snook & Aderton, Inc
Delivery and Shipping
Delivery and Shipping
Fedex ground and freight. Most parts ship same day and arrive within two days.
Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules.
Features:
Flame failure response time of 0.8 or 3.0 seconds.
Flame signal strength ranges from 0.0 to 5.0 Vdc.
Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation.
Flame signal test jacks to measure amplifier flame signal voltage.
Color-coded labels identify flame detection type. Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system 7800 SERIES relay module locks out on safety shutdown with flame detection system failure.
Specifications:
Brand: Honeywell
Manufacturer Part Number: R7847A1033
Cubic Measurement: 0.026
For Use With: Honeywell flame detectors 
Dimensions (LxHxW): 3.85"x5.45"x2.15"
Weight: 0.29LB
Prop 65: No
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.