Honeywell RM7895A1014 Burner Control
Couldn't load pickup availability
Delivery and Shipping
Delivery and Shipping
Fedex ground and freight. Free Shipping on everything!
Description
Description
Microprocessor-based integrated primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls.
Features:
Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
Subbase, amplifier, and prepurge timer are required for operation.
Options include PC interface, keyboard display module, DATA ControlBUS™ Module, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software.
Five LEDs provide sequence information.
Interchangeable plug-in flame amplifiers.
Optional local or remote annunciation of operation and fault information.
Nonvolatile memory retains history files and sequencing status after power loss.
Optional remote reset capability.
Optional report generation.
Selectable relight or lockout on loss of flame.
Airflow switch check.
Specifications:
Manufacturer: Honeywell
Manufacturer Part Number: Honeywell RM7895A1014
Application: On-Off Primary Control with Prepurge
Dimensions (in.): 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
Dimensions (mm): 127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase
Used With: 7800 Series Amplifiers
Weight (lb): 1 lb 15 oz
Weight (kg): 9 kg
Frequency: 50 Hz; 60 Hz (±10%)
Voltage 120 Vac: (+10, -15%)
Shipping and Storage Temperature Range (F): -40 F to +140 F
Shipping and Storage Temperature Range (C): -40 C to +60 C
Flame Establishing Period – Pilot: 4 sec or 10 sec
Flame Establishing Period – Main: Intermittent
Interlocks: Selectable
PrePurge: Determined by ST7800A Purge Timer Card
Required Components: Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card.
Delayed Main Valve: No
Pilot Type: Intermittent
Vibration: 5 G environment