Features:
S8910U 3000 Series has LED Status Indicator and Microammeter Ports for Easy Troubleshooting
For Local (Single Rod) or Remote (Dual Rod) Rectification Type Flame Sensing
Contains Easy to Use Cross Reference and Instructions Plus the Accessories Required to Replace the Existing Hot Surface Ignition Module
Field Selectable Number of Ignition Trials and Trial Time Based on Unit Being Replaced
Specifications:
Manufacturer: Honeywell
Manufacturer Part Number: S8910U3000
Product Type: Ignition Control Module
Fuel Type: Natural/Liquid Propane Gas
Flame Sense Type: Single/Dual Rod
Ignition Source: Internal High Voltage Spark Generator
Ignition Sequence: 1 or 3 Trial
Ignition Trial Time: 4/7 Second
Prepurge Time: 32 Second
Flame Failure Response Time: 1.5 Second
Valve Rating: 2 A @ 24 VAC
Power Rating: 24 VAC @ 50/60 Hz
Temperature Rating: -40 to 175 Degrees F
Lockout Timing: 4/7 Second
Flame Failure Re-Ignition Time: 0.8 Second
Dimensions: 4.6" x 6.35" x 3.05"
Weight: 0.77 lb.