Dynamic Self Check Amp 2/3sec FFRT
The Honeywell R7861A Self-Check Ultraviolet Flame Amplifier is a solid state plug-in amplifier that responds to an ultraviolet signal from a C7061A Self-Check Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
Flame Detection System: Ultraviolet: R7861A, F for use with C7061A Ultraviolet Detector. Flame Failure Response Time: 2 or 3 sec. Flame signal strength ranges from 0.0 to 5.0 Vdc. Compatible with existing Honeywell flame detectors (order separately). Flame Signal: Minimum Acceptable: 1.25 Vdc. Used with Honeywell 7800 SERIES Relay Modules (sold separately).